A43 112-100

General Information

  • Extended Product Type:
    A43 112-100
  • Product ID:
    2CMA100244R1000
  • ABB Type Designation:
    A43 112-100
  • EAN:
    7392696002448
  • Catalog Description:
    Active Energy Class ±1% (or B for MID meters).;
  • Long Description:
    Advanced DIN-rail meter with a large and easy to read back lighted pixel-oriented display. The meter is intended for use in the industry, commercial buildings etc. The meter can be used in 3 or 4 wire systems with a wide voltage range. The meter has several instrumentation values, 25 possible alarms and event logs. Three phase direct connected for active energy. One output for pulses or alarm etc. RS-485 communication over Modbus RTU or EQ Bus. Accuracy class 1.0 (or B for MID meters). The meters is IEC approved + MID approved and verified.

Categories

  • Products » Low Voltage Products and Systems » Modular DIN Rail Products » Energy Efficiency Devices » Energy Meters

Ordering

  • EAN:
    7392696002448
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    90283019

Dimensions

  • Product Net Width:
    123 mm
  • Product Net Height:
    26.5 mm
  • Product Net Depth / Length:
    65 mm
  • Product Net Weight:
    0.448 kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    98 mm
  • Package Level 1 Height:
    68 mm
  • Package Level 1 Depth / Length:
    144 mm
  • Package Level 1 Gross Weight:
    0.538 kg
  • Package Level 1 EAN:
    7392696002448

Environmental

  • Ambient Air Temperature:
    Operation -40 … +70 °C
  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment

Additional Information

  • Accuracy:
    Active Energy Class ±1% (or B for MID meters).
  • Communication Interface:
    Pulse output
  • Communication:
    MODBUS RTU
  • Connecting Capacity Main Circuit:
    1 ... 25 mm²
  • Degree of Protection:
    IP20
  • Enclosure Material:
    Plastic
  • Frequency (f):
    50/60 Hz
  • Function:
    Electricity meter
  • Meter Type:
    Direct connected
  • Mounting Type:
    DIN rail
  • Number of Phases:
    3
  • Product Main Type:
    A43
  • Product Name:
    Electricity Meter
  • Rated Current (In):
    80 A
  • Rated Voltage (Ur):
    3x100 ... 3x500 V
  • RoHS Date:
    2011-44
  • Standards:
    IEC 62052-11, IEC 62053-21, EN 50470-1, EN 50470-3
  • Sub-Function:
    Steel

Certificates and Declarations (Document Number)

Classifications

  • ETIM 4:
    EC001506 - Electronic kilowatt-hour meter
  • ETIM 5:
    EC001506 - Kilowatt-hour meter
  • ETIM 6:
    EC001506 - Kilowatt-hour meter
  • ETIM 7:
    EC001506 - Kilowatt-hour meter
  • Object Classification Code:
    P
  • WEEE Category:
    5. Small Equipment (No External Dimension More Than 50 cm)