Cyberex Power Distribution Unit Highlights

  • Multiple panelboard and breaker configurations offer the highest level of customization for diverse loads
  • Comprehensive system monitoring provides ultimate flexibility for collecting and managing power data
  • Optional safety barrier to separate primary and secondary voltages
  • Branch circuit and sub-feed management (optional) provides enhanced power data collection for branch circuits and sub-feeds
  • Remote monitoring interfaces to building management system using Modbus, web server, and SNMP traps
  • PDU with 320 x 240 high resolution display capable of monitoring and storing data from up to 16 local or remote circuit management devices – each with up to 168 circuits
  • Efficient high isolation, copper wound transformers increases performance and significantly reduce EMI and RFI noise
    Spacious cable management and landing area simplifies frequent wiring changes and ease of installation
  • Easy maintenance access ensures safe and trouble-free repair in minimum time
    Compact footprint maximizes valuable floor space
  • ETL listed to both UL 60950 and UL 891. Suitable for Installation inside or outside IT–Designated spaces 

 

Breakthrough Technology

Circuit Management

Rely on Cyberex’s circuit management solutions to monitor and alert your staff of potential problems before they occur.  Understanding load profiles is the key to proactively managing your data center distribution system and avoiding unnecessary downtime.

  • Branch circuit management – Up to four (4) 42 circuit panel boards (168 poles)
  • Sub-feed circuit management – Up to thirty two (32), 3-wire or twenty four (24), 4-wire sub feed breakers 

Advanced Communication

  • Communicate valuable system data to building management systems (BMS) or local display
  • Protocols available: Modbus RTU, Modbus TCP, BACNET, SNMP trap alarms, Web server

Monitoring system parameters including:

Voltage-current (RMS), MIN Current, MAX Current, kW (power), kVA-load, Power Factor (PF), and Total harmonic distribution (THD) are just a few functions.

Configuration system warnings and alarms including:

Over/under current, over/under voltage, over kW, over THD, low PF, and phase loss are just a few of the warnings and alarm functions.

The image gallery