The basic Test Routine does not require any additional configuration within Field Information Manager.
The only available setting is the selection of the Test Routine to be used, which defines the covered test points:
- 2-Point Test (Others): Signal range is tested at two points of the signal range (25 % and 75 %).
- 5-Point Test (HART): From lower range to upper range value (4, 8, 12, 16, 20 mA)
- 9-Point Test (HART): From lower range to upper range and back to lower range value again (4, 8, 12, 16, 20, 16, 12, 8, 4 mA)