S900 remote I/O

The remote S900 I/O system can be installed directly in zone 1 and zone 2 hazardous areas.

S900 I/O communicates with the control system level using the PROFIBUS standard.
The I/O system can be installed directly in the field, therefore the costs for marshalling and wiring are reduced.

The system is sturdy, error-tolerant and easy to service. Integrated disconnection mechanisms allow replacement during operation, meaning that there is no need to interrupt the primary voltage in order to exchange the power supply units.

S900 I/O features include:

  • Remote I/O system for hazardous areas
  • Redundancy for maximum availability
  • Hot-swap capability of all components during operation
  • Extended diagnostic functions to reduce maintenance efforts

Choose the right hardware

For up to date on technical data for S900 I/O, comparisons, and to generate data sheets, please visit the S900 I/O part of 800xA Hardware Selector:

800XA HARDWARE SELECTOR

Are you looking for support or purchase information?

Benefits
Technical Data
Services
  • Value for your money: Integrated galvanic isolated barrier function reduces the need for additional barriers
  • Simplified maintenance thanks to auto-diagnostics and the availability of diagnostic data via the fieldbus or locally at the S900 I/O station
  • Easy configuration using FDT/DTM or GSD files
Digital I/O Modules
                             Description
DX910S/B/N
    
Digital input or output. Input for dry contact or NAMUR initiator. Output for low power intrinsic safe valves. 8 I/O channels
DP910S/B/N   Frequency input. Input for dry contact or NAMUR initiator
DX910S/B/N
  Digital input or output. Input for dry contact or NAMUR initiator. Output for low power intrinsic safe valves. 8 I/O channels
DO910S/B/N
  Output for valves, 4 channels
DO930N
  With 4 normally-open contacts and 2 changeover contacts
Analog Input Modules

Description
AI910S/B/N


Analog input, 4 channels. Transmitter power supply, 4..20 mA
AI930S/B/N
  Analog input, HART. 4 channels. Transmitter power supply, 4..20 mA
AI931S/B/N
  Analog Input, HART. 4 channels. Passive input, 0/4..20 mA
AI950S/B/N
                            Temperature. 4 channels. Pt100, Pt1000, Ni100 in 2-/3-/4-wire technique thermocouples type B, E, J, K, L, N, R, S, T
isolated inputs channel by channel
Analog Output Modules
  Description
AO910S/B/N
  4 channels. Output 0/4..20 mA.
AO920S/B/N
  4 channels. Output 0/4..20 mA. Isolated outputs channel by channel            
AO930S/B/N
  4 channels. HART. Output 0/4..20 mA.
Device variants:
Safe area mounting: Type N
Zone 2 mounting: Type B
Zone 1 mounting: Type S

Attention: Do not mix Type N, B, S components!

For more data, see the Product Catalog.