Detailed information for: T7H 1250 PR231/P I In=1250A 3p F F

This page contains technical data sheet, documents library and links to offering related to this product. If you require any other information, please contact us using form located at the bottom of the page.

Data Sheet
Downloads
Where to buy online

T7H 1250 PR231/P I In=1250A 3p F F

General Information

  • Extended Product Type:
    T7H 1250 PR231/P I In=1250A 3p F F
  • Product ID:
    1SDA062897R1
  • EAN:
    8015644654467
  • Catalog Description:
    T7H 1250 PR231/P I In=1250A 3p F F
  • Long Description:
    C.BREAKER TMAX T7H 1250 FIXED THREE-POLE WITH FRONT TERMINALS AND LEVER OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC PR231/P-I R 1250

Ordering

  • EAN:
    8015644654467
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85362090

Dimensions

  • Product Net Width:
    210 mm
  • Product Net Height:
    268 mm
  • Product Net Depth / Length:
    154 mm
  • Product Net Weight:
    9.7 kg

Container Information

  • Package Level 1 Units:
    1 piece
  • Package Level 1 Width:
    280 mm
  • Package Level 1 Height:
    350 mm
  • Package Level 1 Depth / Length:
    360 mm
  • Package Level 1 Gross Weight:
    11.2 kg
  • Package Level 1 EAN:
    8015644654467

Environmental

  • RoHS Status:
    Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Conflict Minerals Reporting Template (CMRT):
    9AKK108467A5658
  • Environmental Information:
    9AKK10103A1059
    9AKK108467A6707
  • REACH Declaration:
    9AKK108466A1425
  • RoHS Information:
    9AKK108466A1424
  • SCIP:
    3e621310-1d40-4b47-a236-cae335d0f7ec Italy (IT)
  • Simplified SCIP:
    6a03fcf6-796c-48b6-b9b8-7781e4c585e5 Finland (FI)
    24ba81c5-8c8a-4e1f-900b-c5d2dcef2caf Germany (DE)
    2ed42847-fd9d-428f-bc7b-5b3c95b3ae48 Denmark (DK)
    0fffdfcd-61d3-4b03-9369-066a61f895a5 Poland (PL)
    a2ff2cdd-f7f4-41a1-bb36-8a1c0213366b Croatia (HR)
    5f4834eb-c6d4-46ff-a91d-8667b084336d Netherlands (NL)
    f3114e18-d398-46a2-a9ee-eb9c7382facd Estonia (EE)
    c7a4451f-abd3-45a5-b027-dd2b525e85c5 Greece (GR)
    82fbe619-40a5-428a-bf8f-c13775be773d Portugal (PT)
    c80c29a9-cf45-4e1b-be4a-750c129743bb Bulgaria (BG)
    fc10d938-42c0-42d1-8cbc-f68b669da735 Sweden (SE)
    b1b7aa98-3766-456e-a090-d485792035f0 Poland (PL)
    2015413c-9bde-4fe3-9b47-0da1a1c5b2a7 France (FR)
    e8d11605-1a73-4361-8270-23ff5a825a35 Sweden (SE)
    1be8f87b-3d92-4a68-8e5c-7332f192e2e8 Germany (DE)
    427de604-9a19-4d3c-a326-d7c43a7f1ba7 Germany (DE)
    f9ca64dd-db11-4742-aa0e-f6554636588b Netherlands (NL)
    11ec261f-72bc-4aa0-b335-930cf1cb049d France (FR)
    c54bd71e-48f5-468b-bc98-80923ca3bbd4 Netherlands (NL)
    af0c6999-30b5-4dce-9918-dcc34669bbae Spain (ES)
    434103ea-511e-409d-aa75-6699ff911202 Netherlands (NL)
    3f1065e1-341c-4f90-a7d4-23b5678ed989 Norway (NO)
    c9657c99-fbe0-4326-9e99-18d41a8d21a6 Germany (DE)
    7b93c30a-34a1-457a-ba53-f6835a4bec9f Czech Republic (CZ)
    dc8fc7ae-40b2-4f66-967b-75e059774b1b Netherlands (NL)
    c062c857-aa53-4cc4-86b7-3fb908a007b3 Poland (PL)
  • Toxic Substances Control Act - TSCA:
    9AKK108467A8326

Additional Information

  • Electrical Durability:
    2000 cycle
    60 cycles per hour
  • Mechanical Durability:
    10000 cycle
    60 cycles per hour
  • Number of Poles:
    3
  • Power Loss:
    at Rated Operating Conditions per Pole 47 W
  • Product Main Type:
    SACE Tmax T
  • Product Name:
    Moulded Case Circuit Breaker
  • Product Type:
    Automatic Circuit Breaker
  • Rated Current (In):
    1250 A
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Rated Insulation Voltage (Ui):
    1000 V
  • Rated Operational Voltage:
    690 V AC
  • Rated Service Short-Circuit Breaking Capacity (Ics):
    (220 V AC) 100 kA
    (230 V AC) 100 kA
    (380 V AC) 70 kA
    (400 V AC) 70 kA
    (415 V AC) 70 kA
    (440 V AC) 65 kA
    (500 V AC) 50 kA
    (690 V AC) 31.5 kA
  • Rated Short-time Withstand Current Low Voltage (Icw):
    for 1 s 20 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (220 V AC) 100 kA
    (230 V AC) 100 kA
    (380 V AC) 70 kA
    (400 V AC) 70 kA
    (415 V AC) 70 kA
    (440 V AC) 65 kA
    (500 V AC) 50 kA
    (690 V AC) 42 kA
  • Rated Uninterrupted Current (Iu):
    1250 A
  • Release:
    PR231/P-I
  • Release Type:
    EL
  • Short-Circuit Performance Level:
    H
  • Standards:
    IEC
  • Sub-type:
    T7
  • Suitable For:
    T7
  • Suitable for Product Class:
    Moulded Case Circuit Breakers
  • Terminal Connection Type:
    Fixed Circuit-Breakers
    Front
  • Version:
    F

Certificates and Declarations (Document Number)

Classifications

  • ETIM 4:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 5:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 6:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 7:
    EC000228 - Power circuit-breaker for trafo/generator/installation protection
  • ETIM 8:
    EC000228 - Power circuit-breaker for trafo/generator/installation protection
  • Object Classification Code:
    Q
  • UNSPSC:
    39121100
  • WEEE Category:
    5. Small Equipment (No External Dimension More Than 50 cm)
  • eClass:
    V11.1 : 27370409