Detailed information for: XT1B 160 TMD 32-450 3p F F

This page contains technical data sheet, documents library and links to offering related to this product. If you require any other information, please contact us using form located at the bottom of the page.

Data Sheet
Downloads
Where to buy online
Related Links

XT1B 160 TMD 32-450 3p F F

General Information

  • Extended Product Type:
    XT1B 160 TMD 32-450 3p F F
  • Product ID:
    1SDA066802R1
  • EAN:
    8015644694463
  • Catalog Description:
    XT1B 160 TMD 32-450 3p F F
  • Long Description:
    C.BREAKER TMAX XT1B 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32-450 A

Ordering

  • Order Code US and Canada:
    XT1BE3032AFF000XXX
  • E-Number (Finland):
    3638629
  • EAN:
    8015644694463
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85362090

Dimensions

  • Product Net Width:
    76.2 mm
  • Product Net Height:
    130 mm
  • Product Net Depth / Length:
    70 mm
  • Product Net Weight:
    1.1 kg

Container Information

  • Package Level 1 Units:
    box 1 piece
  • Package Level 1 Width:
    128 mm
  • Package Level 1 Height:
    135 mm
  • Package Level 1 Depth / Length:
    143 mm
  • Package Level 1 Gross Weight:
    1.11 kg
  • Package Level 1 EAN:
    8015644694463

Environmental

  • RoHS Status:
    Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Conflict Minerals Reporting Template (CMRT):
    9AKK108467A5658
  • Environmental Information:
    9AKK107991A8215
    9AKK108467A6707
  • REACH Declaration:
    9AKK108466A1425
  • RoHS Information:
    9AKK108466A1424
  • SCIP:
    f73e4266-0af4-4cef-b9b3-260c00a910f9 Italy (IT)
  • Simplified SCIP:
    06390208-d394-410e-9842-b8f1aa84ad09 Poland (PL)
    ce31830e-4feb-4262-8ac1-c0a505cbd58c Norway (NO)
    43aad17a-9e80-44f3-9db3-9d6d35642925 Finland (FI)
    e181dcff-17e3-4829-8167-be0ead9f9f4f Netherlands (NL)
    7515b418-fb55-4766-95e2-4323a6ecd612 Germany (DE)
    45a6cb81-5081-41fe-a071-5cf38b8adf65 Denmark (DK)
    ff639201-5b12-440f-821d-3a6c4ce2953c Germany (DE)
    f913e764-1c76-4c93-9fc0-2a0875805dc8 Croatia (HR)
    dc0ff913-83d0-4f15-babc-7a856a1b3255 Czech Republic (CZ)
    b020eaeb-cf23-445c-95a4-4f103ce43fa5 Poland (PL)
    fa9663ae-4d74-4267-a4b0-fcfc539c2914 Netherlands (NL)
    a409c160-db3e-4860-adba-1d89501dd2c5 Netherlands (NL)
    aebf759a-29ca-419e-b416-0ecf3b3f9577 Estonia (EE)
    e0db3e96-345c-4b56-91d0-3a02a89a2482 Greece (GR)
    094c590f-e054-4452-9a76-5fb143f976e9 Portugal (PT)
    2e656ab5-eff3-4755-bcc3-052950d58ddb Bulgaria (BG)
    df9ecf69-1483-4540-b0c4-3bdfc49abdad Sweden (SE)
    c6236bbe-bf16-4be7-9c71-7d042fe7dbe1 Poland (PL)
    d6074c8c-4abc-41ae-ad9f-fa07173c3572 France (FR)
    382fe93d-82da-457d-b30e-7032f1b8681e Sweden (SE)
    908a3719-74a3-4ad9-8c4f-413f7b640fe2 Germany (DE)
    c0dd578e-17bc-4735-a4bd-35aac606fc6d Germany (DE)
    f358ac58-4638-4878-b499-0f7191ed7405 France (FR)
    efc96197-3e4f-4d77-a0c4-4a5c216675e2 Netherlands (NL)
    9131538b-9a93-4dc4-88d8-690a0b2651e3 Spain (ES)
    d203dbb9-dd7c-4d5d-ad5c-3e96966e8826 Netherlands (NL)
  • Toxic Substances Control Act - TSCA:
    9AKK108467A8326

Additional Information

  • Circuit Breaker Type to be Associated:
    Power Distribution
  • Connecting Capacity Main Circuit:
    Busbar 45.5 ... 80 mm²
  • Current Type:
    AC/DC
  • Electrical Durability:
    120 cycles per hour
    8000 cycle
  • Mechanical Durability:
    240 cycles per hour
    25000 cycle
  • Number of Poles:
    3
  • Opening Time:
    CB with SOR 15 ms
    CB with UVR 15 ms
  • Order Multiple:
    1 piece
  • Power Loss:
    at Rated Operating Conditions per Pole 2.1 W
  • Product Main Type:
    SACE Tmax XT
  • Product Name:
    Moulded Case Circuit Breaker
  • Product Type:
    Automatic Circuit Breaker
  • Rated Current (In):
    32 A
  • Rated Frequency (f):
    50 / 60 Hz
  • Rated Voltage (Ur):
    690 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Rated Instantaneous Short-Circuit Current Setting (Ii):
    450 A
  • Rated Insulation Voltage (Ui):
    800 V
  • Rated Operational Voltage:
    690 V AC
    500 V DC
  • Rated Service Short-Circuit Breaking Capacity (Ics):
    (220 V AC) 25 kA
    (230 V AC) 25 kA
    (240 V AC) 25 kA
    (380 V AC) 18 kA
    (415 V AC) 18 kA
    (440 V AC) 11.25 kA
    (500 V AC) 8 kA
    (525 V AC) 6 kA
    (690 V AC) 3 kA
    (250 V DC) 2 Poles in Series 18 kA
    (500 V DC) 3 Poles in Series 18 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (220 V AC) 25 kA
    (230 V AC) 25 kA
    (240 V AC) 25 kA
    (380 V AC) 18 kA
    (415 V AC) 18 kA
    (440 V AC) 15 kA
    (500 V AC) 8 kA
    (525 V AC) 6 kA
    (690 V AC) 3 kA
    (250 V DC) 2 Poles in Series 18 kA
    (500 V DC) 3 Poles in Series 18 kA
  • Rated Uninterrupted Current (Iu):
    160 A
  • Recommended Screw Driver:
    Main Circuit M6
  • Release:
    TMD
  • Release Type:
    TM
  • Setting Range:
    22.4...32 A
  • Short-Circuit Performance Level:
    B
  • Standards:
    IEC
  • Sub-type:
    XT1
  • Terminal Connection Type:
    Front
  • Terminal Type:
    Bolt
  • Tightening Torque:
    6 N·m
  • Version:
    F
  • CAD Dimensional Drawing:
    1SDH001295R0008

Certificates and Declarations (Document Number)

Classifications

  • ETIM 4:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 5:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 6:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 7:
    EC000228 - Power circuit-breaker for trafo/generator/installation protection
  • ETIM 8:
    EC000228 - Power circuit-breaker for trafo/generator/installation protection
  • Object Classification Code:
    Q
  • WEEE Category:
    5. Small Equipment (No External Dimension More Than 50 cm)
  • eClass:
    V11.1 : 27370409