Detailed information for: XT2H 160 TMD 10-100 3p F F

This page contains technical data sheet, documents library and links to offering related to this product. If you require any other information, please contact us using form located at the bottom of the page.

Data Sheet
Downloads
Where to buy online
Related Links

XT2H 160 TMD 10-100 3p F F

General Information

  • Extended Product Type:
    XT2H 160 TMD 10-100 3p F F
  • Product ID:
    1SDA067592R1
  • EAN:
    8015644014889
  • Catalog Description:
    XT2H 160 TMD 10-100 3p F F
  • Long Description:
    C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 10-100 A

Ordering

  • Order Code US and Canada:
    XT2HE3010AFF000XXX
  • EAN:
    8015644014889
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85362090

Dimensions

  • Product Net Width:
    90 mm
  • Product Net Height:
    130 mm
  • Product Net Depth / Length:
    82.5 mm
  • Product Net Weight:
    1.4 kg

Container Information

  • Package Level 1 Units:
    box 1 piece
  • Package Level 1 Width:
    130 mm
  • Package Level 1 Height:
    208 mm
  • Package Level 1 Depth / Length:
    145 mm
  • Package Level 1 Gross Weight:
    1.2 kg
  • Package Level 1 EAN:
    8015644014889

Environmental

  • RoHS Status:
    Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Conflict Minerals Reporting Template (CMRT):
    9AKK108467A5658
  • Environmental Information:
    9AKK107991A8215
    9AKK108467A6707
  • REACH Declaration:
    9AKK108466A1425
  • RoHS Information:
    9AKK108466A1424
  • SCIP:
    c22196a0-44f2-434b-9b84-a46b82990e7c Italy (IT)
  • Simplified SCIP:
    9d9ec041-1e11-4537-a4a1-57fac441dd18 Poland (PL)
    a0f5e33e-67fa-47f6-ae5e-79e0811a5495 Norway (NO)
    2a97fe19-98a9-41fb-a519-dcb14e5ca45d Finland (FI)
    54a51eeb-76b0-4ed9-951d-dbd62e42d812 Netherlands (NL)
    9d675f1e-7b93-4032-b982-8713fa095a72 Germany (DE)
    141d392c-d8b2-4e1a-9c1f-d6f02ea85951 Denmark (DK)
    1783be2d-0c1c-4b7a-bc93-08b6ea185436 Netherlands (NL)
    2f6a1fb8-3be0-44bd-9b25-332a278974d5 Netherlands (NL)
    4f1cde91-7ef3-4cf9-b6fe-f94495c73439 Estonia (EE)
    5af5b789-0f6f-4562-a273-94c8798c12e8 Greece (GR)
    7582d9bf-de04-4f66-974d-7d9b9bd6a387 Portugal (PT)
    ba5f248a-53e9-4587-a247-8f22ab8c6f93 Germany (DE)
    0ba068b1-6608-4680-bc9d-429c1eabe785 Croatia (HR)
    ca6ad635-5242-4ae4-9431-d272b28c3e65 Czech Republic (CZ)
    052a0e46-58d2-4fb7-a5b6-934e8a8dc6f6 Poland (PL)
    f04494fe-8119-4d21-b6ca-07e9c0b625a8 Germany (DE)
    84e157f2-3374-40a5-8c78-717ccf5c7846 Germany (DE)
    44e6a526-b658-4d70-b5db-4867dd9e9a20 France (FR)
    18dec544-d410-4f00-b38d-92b9c0bf3903 Netherlands (NL)
    f39691fb-7611-4849-8846-02b8de563d72 Spain (ES)
    a502b64f-be66-4bf4-8e80-9ec1c499f3ab Netherlands (NL)
    8510d6a1-f92e-4fd6-81d5-9f8d61095d80 Bulgaria (BG)
    a66a5e17-79eb-4e54-b064-2a285af77eb5 Sweden (SE)
    5384096f-1658-431d-ab1e-e2b7a3961154 Poland (PL)
    f444016d-f8a6-4613-b9da-2a90df11fd16 France (FR)
    07e7c4ed-1ab7-45d7-a3b9-a4d35ed4af63 Sweden (SE)
  • Toxic Substances Control Act - TSCA:
    9AKK108467A8326

Additional Information

  • Circuit Breaker Type to be Associated:
    Power Distribution
  • Connecting Capacity Main Circuit:
    Busbar 32.5..100 mm²
  • Current Type:
    AC/DC
  • Electrical Durability:
    120 cycles per hour
    8000 cycle
  • Mechanical Durability:
    240 cycles per hour
    25000 cycle
  • Number of Poles:
    3
  • Opening Time:
    CB with SOR 15 ms
    CB with UVR 15 ms
  • Order Multiple:
    1 piece
  • Power Loss:
    at Rated Operating Conditions per Pole 2.95 W
  • Product Main Type:
    SACE Tmax XT
  • Product Name:
    Moulded Case Circuit Breaker
  • Product Type:
    Automatic Circuit Breaker
  • Rated Current (In):
    10 A
  • Rated Frequency (f):
    50 / 60 Hz
  • Rated Voltage (Ur):
    690 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Rated Instantaneous Short-Circuit Current Setting (Ii):
    100 A
  • Rated Insulation Voltage (Ui):
    1000 V
  • Rated Operational Voltage:
    690 V AC
    500 V DC
  • Rated Service Short-Circuit Breaking Capacity (Ics):
    (220 V AC) 100 kA
    (230 V AC) 100 kA
    (240 V AC) 100 kA
    (380 V AC) 70 kA
    (415 V AC) 70 kA
    (440 V AC) 65 kA
    (500 V AC) 50 kA
    (525 V AC) 30 kA
    (690 V AC) 15 kA
    (250 V DC) 2 Poles in Series 70 kA
    (500 V DC) 3 Poles in Series 70 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (220 V AC) 100 kA
    (230 V AC) 100 kA
    (240 V AC) 100 kA
    (380 V AC) 70 kA
    (415 V AC) 70 kA
    (440 V AC) 65 kA
    (500 V AC) 50 kA
    (525 V AC) 30 kA
    (690 V AC) 15 kA
    (250 V DC) 2 Poles in Series 70 kA
    (500 V DC) 3 Poles in Series 70 kA
  • Rated Uninterrupted Current (Iu):
    160 A
  • Recommended Screw Driver:
    Main Circuit M6
  • Release:
    TMD
  • Release Type:
    TM
  • Setting Range:
    7...10 A
  • Short-Circuit Performance Level:
    H
  • Standards:
    IEC
  • Sub-type:
    XT2
  • Terminal Connection Type:
    Front
  • Terminal Type:
    Bolt
  • Tightening Torque:
    6 N·m
  • Version:
    F
  • CAD Dimensional Drawing:
    1SDH002230A1001

Certificates and Declarations (Document Number)

Classifications

  • ETIM 4:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 5:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 6:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 7:
    EC000228 - Power circuit-breaker for trafo/generator/installation protection
  • ETIM 8:
    EC000228 - Power circuit-breaker for trafo/generator/installation protection
  • Object Classification Code:
    Q
  • UNSPSC:
    39120000
  • WEEE Category:
    5. Small Equipment (No External Dimension More Than 50 cm)
  • eClass:
    V11.1 : 27370409
  • Contact us

    Submit your inquiry and we will contact you

    Contact us
Select region / language