Detailed information for: XT2H 160 TMA 160-1600 4p F F InN=100%

This page contains technical data sheet, documents library and links to offering related to this product. If you require any other information, please contact us using form located at the bottom of the page.

Data Sheet
Downloads
Where to buy online
Related Links

XT2H 160 TMA 160-1600 4p F F InN=100%

General Information

  • Extended Product Type:
    XT2H 160 TMA 160-1600 4p F F InN=100%
  • Product ID:
    1SDA067627R1
  • EAN:
    8015644015237
  • Catalog Description:
    XT2H 160 TMA 160-1600 4p F F InN=100%
  • Long Description:
    C.BREAKER TMAX XT2H 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 160 I3=800...1600 A FULLY RATED NEUTRAL

Ordering

  • Order Code US and Canada:
    XT2HE4160BFF000XXX
  • EAN:
    8015644015237
  • Minimum Order Quantity:
    1 piece
  • Customs Tariff Number:
    85362090

Dimensions

  • Product Net Width:
    120 mm
  • Product Net Height:
    130 mm
  • Product Net Depth / Length:
    82.5 mm
  • Product Net Weight:
    1.6 kg

Container Information

  • Package Level 1 Units:
    box 1 piece
  • Package Level 1 Width:
    130 mm
  • Package Level 1 Height:
    208 mm
  • Package Level 1 Depth / Length:
    145 mm
  • Package Level 1 Gross Weight:
    2.101 kg
  • Package Level 1 EAN:
    8015644015237

Environmental

  • RoHS Status:
    Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Conflict Minerals Reporting Template (CMRT):
    9AKK108467A5658
  • Environmental Information:
    9AKK107991A8215
    9AKK108467A6707
  • REACH Declaration:
    9AKK108466A1425
  • RoHS Information:
    9AKK108466A1424
  • SCIP:
    faa3f41f-8e61-4b91-a07b-0511a963944a Italy (IT)
  • Simplified SCIP:
    60a571f5-3995-40b3-bb49-1f11025e1807 Norway (NO)
    c5ed6e67-4749-4b2d-932d-f3ef7de7429e Finland (FI)
    dea9951f-fe91-4b90-a5ac-4c4b9aa83f4d Netherlands (NL)
    2fb06f6f-179e-4c09-8639-d4d63fecc4a1 Germany (DE)
    1ead897c-f009-4721-a055-fb14f0466a41 Denmark (DK)
    aab8bcc9-e7a8-41b6-9b79-8c4a80db47e7 Netherlands (NL)
    d31902ec-b49c-488c-8549-32b80cc76379 Netherlands (NL)
    adaceaea-852c-429a-8d3e-671ac095aa06 Estonia (EE)
    5e7686f0-862d-484f-a2bb-643aec8a2b32 Greece (GR)
    3f6eb64c-9ef0-43b2-b18c-bf5730a12049 Portugal (PT)
    570d9a49-b217-4f41-ae89-8d7cefbacc00 Germany (DE)
    d8cda10f-1790-4ebf-b4f3-be09afda7e3e Croatia (HR)
    7f4a32e3-1b4f-4d23-9f5d-d3bb9c4f57dc Czech Republic (CZ)
    ab6edb75-3838-4598-9763-3b0f985814a8 Poland (PL)
    58b1600a-81c9-49d9-ad45-879c5081e6e8 Germany (DE)
    f48e9ad7-4c91-4613-a6f1-d071cce66ee6 Germany (DE)
    bba7cff5-5854-4af1-b8a0-591df187d1c6 France (FR)
    de3ffc45-8d4a-4112-a65f-649200337fee Netherlands (NL)
    8abb20d7-4a55-4921-a3f3-5c6c59b130bb Spain (ES)
    31fd3c19-6def-462b-8679-a424495abf89 Netherlands (NL)
    4112504e-f9ca-4eb0-91fe-eeec620426ec Bulgaria (BG)
    f90e61fc-0e9b-4145-aeb0-bff1c6ea6a91 Sweden (SE)
    25c39475-3da8-418b-bdaa-b30159b9c9ae Poland (PL)
    95c15571-9d49-4e79-ab92-f4228c724cdd France (FR)
    356a6754-a76d-4f59-ac81-3ce4e44deb82 Sweden (SE)
    c1481159-c29c-431d-9a47-5e94a08d116c Poland (PL)
  • Toxic Substances Control Act - TSCA:
    9AKK108467A8326

Additional Information

  • Circuit Breaker Type to be Associated:
    Power Distribution
  • Connecting Capacity Main Circuit:
    Busbar 32.5..100 mm²
  • Current Type:
    AC/DC
  • Electrical Durability:
    120 cycles per hour
    8000 cycle
  • Mechanical Durability:
    240 cycles per hour
    25000 cycle
  • Number of Poles:
    4
  • Opening Time:
    CB with SOR 15 ms
    CB with UVR 15 ms
  • Order Multiple:
    1 piece
  • Power Loss:
    at Rated Operating Conditions per Pole 16.15 W
  • Product Main Type:
    SACE Tmax XT
  • Product Name:
    Moulded Case Circuit Breaker
  • Product Type:
    Automatic Circuit Breaker
  • Rated Current (In):
    160 A
  • Rated Frequency (f):
    50 / 60 Hz
  • Rated Voltage (Ur):
    690 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Rated Instantaneous Short-Circuit Current Setting (Ii):
    800…1600 A
  • Rated Insulation Voltage (Ui):
    1000 V
  • Rated Operational Voltage:
    690 V AC
    500 V DC
  • Rated Service Short-Circuit Breaking Capacity (Ics):
    (220 V AC) 100 kA
    (230 V AC) 100 kA
    (240 V AC) 100 kA
    (380 V AC) 70 kA
    (415 V AC) 70 kA
    (440 V AC) 65 kA
    (500 V AC) 50 kA
    (525 V AC) 30 kA
    (690 V AC) 15 kA
    (250 V DC) 2 Poles in Series 70 kA
    (500 V DC) 3 Poles in Series 70 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (220 V AC) 100 kA
    (230 V AC) 100 kA
    (240 V AC) 100 kA
    (380 V AC) 70 kA
    (415 V AC) 70 kA
    (440 V AC) 65 kA
    (500 V AC) 50 kA
    (525 V AC) 30 kA
    (690 V AC) 15 kA
    (250 V DC) 2 Poles in Series 70 kA
    (500 V DC) 3 Poles in Series 70 kA
  • Rated Uninterrupted Current (Iu):
    160 A
  • Recommended Screw Driver:
    Main Circuit M6
  • Release:
    TMA
  • Release Type:
    TM
  • Setting Range:
    112...160 A
  • Short-Circuit Performance Level:
    H
  • Standards:
    IEC
  • Sub-type:
    XT2
  • Terminal Connection Type:
    Front
  • Terminal Type:
    Bolt
  • Tightening Torque:
    6 N·m
  • Version:
    F
  • CAD Dimensional Drawing:
    1SDH002230A1002

Certificates and Declarations (Document Number)

Classifications

  • ETIM 4:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 5:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 6:
    EC000228 - Power circuit-breaker for trafo/generator/installation prot.
  • ETIM 7:
    EC000228 - Power circuit-breaker for trafo/generator/installation protection
  • ETIM 8:
    EC000228 - Power circuit-breaker for trafo/generator/installation protection
  • Object Classification Code:
    Q
  • UNSPSC:
    39120000
  • WEEE Category:
    5. Small Equipment (No External Dimension More Than 50 cm)
  • eClass:
    V11.1 : 27370409