Cyberex Digital Three Phase Charger Specifications

¿Necesita más información?

General data

Current Ratings

25, 30, 40, 50, 75, 100, 125, 150, 200, 250, 300, 400, 500, 600, 800, 1000 A

AC Input

Voltage

208, 240, 480 or 550–600VAC 60Hz
220, 380, or 416VAC 50/60Hz

Voltage range

+10%, -12%

Input Frequency Tolerance
±5%
Efficiency
85-90% typical for 130VDC at 50-100% load
DC Output
Voltage ratings 12, 24, 48, or 130 VDC nominal
Continuous ratings 110% rated current at maximum equalized voltage at 50º C
Voltage regulation ± 0.25% for line, load, frequency and temperature variations
Electrical noise 32dBrnc
Ripple 12/24/48VDC – Unfiltered on battery 1% Vrms
– Filtered on battery 30mVrms
– Filtered off battery 1% Vrms
– Battery Eliminator 30mVrms
130VDC: – Unfiltered on battery 2% Vrms
– Filtered on battery 100mVrms
– Filtered off battery 2% Vrms
– Battery Eliminator 100mVrms
 Surge Withstand Capability  Meets IEEE-472/ANSI C37.90a

Communications

User interface/indications

Digital LED Meter

Communication ports

Modbus and Ethernet Communications ports available

Environmental

Operating ambient temperature

0–122°C (-18º C to 50º C) without derating

Operating altitude

10,000 feet (3,000 meters) above sea level without derating load

Relative humidity 5-95% non-condensing
Audible noise Less than 65 dBA at any point 5ft. (1.5m) from any vertical surface of enclosure

Technical specifications are subject to change without notice. 


Select region / language