40kW–1.2MW
|
40kW
|
240kW
|
1.0 |
Online double conversion, transformerless, modular,
Decentralized Parallel Architecture |
Up to 6 modules in one frame / up to 5 frames in parallel |
Bottom |
Front access only |
Built-in (standard) |
5-wires, 3-phase + neutral + ground |
3 x 415/240V + neutral + ground
|
< 100% (–15%, +10%),
< 80% (–20%, +10%),
< 60% (–30%, +10%) |
< 4% at 100% load |
50/60Hz ± 5% |
0.99 @ 100% load |
Yes |
Nominal input voltage |
3 x 415/240V + neutral + ground
|
Voltage tolerance |
± 2.5% |
Voltage distortion THDv |
< 2% in linear mode |
Frequency |
50/60Hz |
Up to 95.6% at nominal load |
Protection rating |
IP 20 |
Storage temperature |
−25° to +70°C
|
Operating temperature |
0° to +40°C |
Altitude (above sea level) |
1000 m without de-rating |
Number of 12V jars/string |
42 – 50 jars
|
Types |
VRLA, NiCd |
Battery charger |
Decentralized charger in each module set |
Graphical touch screen (one per frame as standard)
Decentralized LCD + mimic diagram (one per module as standard) |
USB, RS-232, voltage-free contacts, SNMP (optional) |
Remote shutdown, gen-set interface, external bypass contact |
UL 1778 5th edition, CSA C22.2 No. 107.3-14 Third Edition |
IEC/EN 62040-2 C3 |
ISO 9001:2008 |
1517 lbs. (688 kg) |
31.16" x 77.76" x 35.17" (791 x 893 x 1975.5 mm) |
Note: Please refer to ABB Conceptpower DPA 240 technical documents for configurations, features, recommendations and guidelines.