Nominal voltage | ups to 6.6 kV |
Current rating | 600 A |
Power system type | 3-Phase (3-Wire) IT or TN |
Nominal frequency | 50 or 60 Hz |
Basic Impulse Level (BIL) | 60 kV |
Capacity Rating | Up to 6.0 MVA |
Displacement Power Factor | 0.7 lagging to 0.9 leading |
Transfer time | ≤ 1.8 ms (typical) |
Autonomy time | up to 15 min. |
Frequency accurancy | 0.10% (inverter operation) |
Voltage accurancy | ± 5.0% (inverter operation) |
Voltage distortion | < 2.5% THDv for linear loads |
Nominal DC Voltage | 750 V dc |
Discharging Voltage Range | 812 V dc to 554 V dc |
Recharge power | typically 10% of rated kVA |
Storage technology | Ultracapacitors, flywheels or batteries (lead acid, Li-Ion) |
Minimum output voltage | > 95% at end of discharge |
Efficiency | 99.5% (typical) |
MV enclosure IP rating | IP23 |
LV enclosure IP rating | IP20 |
IEC pollution degree rating | 3 |
Operating temperature | 0°C to 40°C (excluding energy storage) |
Noise | 75 dBA typical at 1 m |
Cooling | forced air cooled |
Material | Electro-galvanized steel |
Color | RAL 7035 |
Enclosure access
| Hinged doors with key lock |
Tpe | Color LCD Touchscreen |
Communication type | Modbus TCP, web server, digital I/O |
Quality | ISO 9001 |
Performance | IEC 62040-3, VFD SS 211 |
Construction and safety | IEC 60664-1
IEC 62271-200 |
Le specifiche tecniche sono soggette a modifica senza preavviso.