| System power rating |
1000, 1100, 1200, 1250, 1350 for 415V systems
1000, 1100, 1200, 1500, 1600 for 480V systems |
Core power rating
|
337 single power blocks @ 415V
400 single power blocks @ 480V
|
Topology
|
Online double conversion
|
Parallel system capacity
|
Up to 4 UPS systems via RPA Decentralized Architecture
|
Static bypass inductor (standard)
|
Up to 25% more flexibility on cable length in case of RPA system
|
Cable entry
|
Top or bottom
|
Serviceability
|
Front and top service access
|
HRG ready
|
Yes
|
Input connections
|
Single or dual feed
|
Short circuit withstand rating
|
100 kAIC
|
Static bypass
|
100% rated - continuous duty
|
Cabinet color
|
RAL 9005 (black)
|
|
|
|
Nominal input voltage
|
415 VAC, 3-ph, 4 W + ground
480 VAC, 3-ph, 3 W + ground
|
Voltage tolerance
|
-15% to +15%
|
| Current distortion THDi |
<3.0% 100% load normal mode - linear
|
Frequency range
|
60 Hz +/-10%
|
Power factor
|
0.99 |
|
|
|
Rated output voltage
|
415 VAC, ph-ph / 240 VAC ph-N
480 VAC, ph-ph
|
Voltage tolerance
|
Static +/-1%
Dynamic (step load 0%-100%-0) +/-3
Dynamic (step load 0%-50%-0) +/-2
|
Voltage distortion THDu
|
<3 @ 100% load, nominal mode - linear
<5 @ 100% load, nominal mode - non-linear
|
Frequency
|
60 Hz
|
Rated power factor
|
1.0
|
|
|
|
Double conversion (VFI)
|
Up to 97%
|
eBoost mode (VFD)
|
Up to 99%
|
|
|
|
| Protection rating |
IP20 |
| Storage temperature |
-13 to 131°F / -25 to 55°C
|
| Operating temperature |
32 to 104°F / 0 to 40°C
|
| Altitude without de-rating |
Up to 1,000 m |
| Altitude with de-rating |
1,500 m: -2.5% / 2,500 m: -2.5%
1,500 m: -2.5% / 1,500 m: -2.5%
|
| Acoustic noise at 1 m |
<80 dBA |
|
|
|
| User interface |
System graphical touch screen |
| Communication ports |
RS232, SNMP & Modbus |
| Customer interface |
Remote shutdown, gen-set interface, external bypass contact |
|
|
|
| Type |
Lithium ion, VRLA, VLA, NiCd & Ni-Zn |
| Nominal battery bus |
480V (240 Cell) |
|
|
|
| Safety |
ETL as tested to UL 1778
UL 9540
EN 62040-1 |
| EMC |
C3 |
| Manufacturing |
ISO 9001:2015, ISO 14001:2015, OHSAS18001 |
|
|
|
Weights [lbs] [kgs]
Dimensions w x h x d [in] [mm] |
415V systems
1,000 kW
8,157 lbs / 3,700 kgs
1,100, 1,200 & 1,250 & 1,350 kW
9,039 lbs / 4,900 kgs
480V systems
1,000, 1,100, & 1,200 kW
8,157 lbs / 3,700 kgs
1,500 & 1,600
9,039 lbs / 4,900 kgs
415V & 480V systems
129.92 x 86.61 x 39.37 in
3,300 x 2,200 x 1,000 mm
|
| Changes to specifications are reserved and subject to change. |