Rated Supply Voltage (according to model)
|
220 V (208 – 220 V)
400 V (380 – 400 V)
480 V (415 - 480 V)
Note: Operation at lower than the rated voltage results in less kVA per module. Consult the rating tables for more information
|
Voltage tolerance
|
± 10%
|
Nominal supply frequency
|
50 Hz or 60 Hz
|
Frequency tolerance
|
± 5 Hz
|
Maximum Continuous Voltage
|
110%
|
Power system
|
3 phase + Neutral (4-Wire) Centre ground referenced (TN-S)
Contact us for use in other power systems |
Overvoltage category
|
III
|
Fault capacity
|
Refer to the model tables in the PCS100 UPS-I technical catalogue
|
Efficiency (400 V & 480 V models)
|
99% (typical)
|
Efficiency (220 V models) |
98% (typical) |
Overload and Short Circuit Protection |
Circuit Breaker (not included) |
Overload Capacity |
120% for 60 s
150% for 30 s
200% for 10 s
300% for 5 s
Not more than once every 10 minutes. For more information refer to the PCS100 UPS-I technical catalogue |
Capacity Rating
|
150 kVA to 3000 kVA
|
Displacement Power Factor of Connected Load
|
0.5 lagging to 0.9 leading
|
Crest Factor for Rated kVA
|
2.0
|
Maximum allowed motor load
|
25% of rated kVA
Contact ABB for applications with greater than 25%
|
Overload Capability – Inverter
|
110% for 30 s
|
Maximum operating period
|
30 s at rated load
|
Transfer time
|
≤ 1.8 ms (typical)
|
Voltage Settling time
|
≤ 5 ms (typical)
|
Cooling
|
Air cooled, fan forced |
Minimum output voltage |
> 95% at end of discharge |
Output Frequency |
50 or 60 Hz
Inverter frequency equals the supply frequency.
|
Frequency accuracy |
0.10% |
Overload capability |
110% for 30 s |
Voltage distortion |
< 2.5% THDv for linear loads |
Voltage unbalance
(negative / positive sequence) |
<3% for 100% unbalanced loads
|
Fault capacity (short circuit) |
120% of rated current |
900 A Utility Disconnect
|
Integrated normally closed contactors
|
2200 A & 4200 A Utility Disconnect
|
Optional air circuit breaker (ACB)
|
Overload Capability |
150% for 500 s
200% for 300 s
300% for 120 s
500% for 30 s
Note: Not more than once every 30 minutes. |
Closing Time 900 A |
20 ms |
Closing Time 2200 & 4200 A |
80 ms |
Cooling |
Convection |
Capacity Rating
|
110% of PCS100 UPS-I kVA rating for 30 s
Note: Optimized for short-term performance.
|
Type
|
Dry
|
UL Insulation Class
|
N (200 °C)
|
Design Temperature |
Temperature rise 60 °C for short-term full load operation |
Typical Impedance |
8%
Note: The PCS100 UPS-I incorporates impedance voltage compensation control methods
|
System DC Nominal Voltage
|
750 V DC |
Discharging Voltage Range |
750 V DC to 554 V DC |
Overload Capacity |
100% |
Rated power |
300 kW per string |
Autonomy period |
2 s @ 300 kW
For more information refer to the autonomy calculations in refer to the PCS100 UPS-I technical catalogue |
Operationg tempertaure |
15 °C to 25 °C (recommended) |
Design life |
15 years at 25 °C |
Cycle Life |
> 500,000 |
Recharge time |
< 45 s |
System DC Nominal Voltage
|
672V DC (56 x 12V DC)
|
Discharging Voltage Range |
780 V DC to 554 V DC
|
Overload Capacity |
100% |
Rated power |
240 kW per string |
Autonomy period |
30 s @ 240 kW
For more information refer to ABB Document 2UCD120000E018
|
Operationg tempertaure |
15 °C to 25 °C (recommended) |
Design life |
10 years at 25 °C |
Cycle Life |
> 800 (full load 30 s discharge) |
Recharge time |
< 30 min |
System DC Nominal Voltage |
672 V DC (56 x 12V DC) |
Dsicharging Voltage Range |
780 V DC to 554 V DC |
Measurement Method
|
Line to Line
|
Sample Time
|
125 µs
|
Resolution of time stamp in event log
|
10 ms |
Measurement Type
|
Half-cycle RMS according to IEC 61000-4-30
|
Operating temperature range
|
0° C to 40° C
32° F to 104° F
|
Operating altitude
|
1< 1000 m without derating
|
Capacity derating with altitude
|
1% every 100 m
above 1000 m
2000 m maximum
|
Humidity
|
< 95%, non-condensing
|
Pollution degree rating
|
2 |
Noise |
< 75dBA @ 2 m |
Enclosure rating |
IP20 / NEMA 1
|
Material |
Electro-galvanized steel
|
Panel Thickness Side and Rear10 ms |
1.5 mm |
Panel Thickness Door
|
2 mm
|
Finish |
Standard epoxy-polyester powder coating textured finish |
Color |
RAL7035 |
Enclosure Access |
Hinged doors with key lock |
User Interface
|
10.1” color touch panel
|
Touch panel
|
Full parameter control
|
Control inputs
|
Start / Stop / Reset digital inputs
|
Control outputs
|
Running, warning and fault relays
|
Access protocol
|
Ethernet connectivity
Modbus TCP
|
Quality |
ISO 9001 |
Marking |
CE |
Construction and safety |
IEC 62040-1 |
Electromagnetic Compatibility |
IEC 62040-2, Category C3 |
Performance |
IEC 62040-3,
VFD SX 211 ≤ 450 kVA
VFD SS 211 > 450 kVA |
Technical specifications are subject to change without notice.