General data 

UPS frame rated power

300 kW

UPS module rated power

50 kW

UPS output rated PF

1.0

Max no of parallel frames

Up to 5 frames 

Max no of parallel modules across frames

Up to 30 modules

Max system power

1500 kW

Wiring

3ph + N + PE

UPS type

Modular (DPA)

Topology

Online double conversion

Input

Nominal input voltage

220/380, 230/400, 240/415 VAC

Voltage range

161/280 - 264/460 VAC

Frequency range

35 - 70 Hz 

Current THD at 100% load

< 3%

Power Factor at 100% load

≥ 0.99

Output

Rated output voltage (load dependent)

220/380, 230/400, 240/415 VAC

Voltage THD (with linear load)

< 2% 

Rated frequency

50 or 60 Hz (selectable)

Efficiency

Double conversion

Up to 97.6% module efficiency,
up to 97.4% system efficiency

Eco-mode

99%

Communications

User interface

Module level LCD + mimic diagram System graphical display

Communication ports

USB, RS-232, SNMP slot, potential-free contacts

Software

Monitoring and shutdown software available as option