DPA UPScale ST S2 technical specifications

Are you looking for support or purchase information?

General data 

System power range

10 kW – 200 kW

UPS module rated power
10 / 20 kW

UPS frame rated power

80 / 60 / 120 / 200 kW

UPS output rated PF

1.0

Max.power per frame

200 kW / 10 modules

Max no. of parallel modules across frames  20 modules / up to 4 frames

Wiring

3ph + N + PE

UPS type

Modular (DPA)

Topology

True online double conversion

Input

Nominal input voltage

220/380, 230/400, 240/415 VAC

Voltage range

150/204 - 264/460 VAC (load dependent)

Frequency range

35-70 Hz 

Current THD at 100% load

< 3 %

Power Factor at 100% load

≥ 0.99

Output

Rated output voltage

220/380, 230/400, 240/415 VAC

Voltage THD (with linear load)

< 1.5 % 

Frequency

50 or 60 Hz (selectable)

Efficiency

Online double conversion

Up to 96%

Eco-mode

98%

Communications

User interface module level

LCD control panel + mimic diagram

User interface system level Graphical display (option)

Communication ports

USB, RS-232, SNMP slot, potential-free contacts

Software

Monitoring and shutdown software available as option

Compliancy

Safety

IEC/EN 62040-1

EMC

IEC/EN 62040-2

Performance

IEC/EN 62040-3

Manufacturing

ISO 9001:2008, ISO 14001:2004

Technical specifications are subject to change without notice. 