S800-eA I/O - open process I/O system

Scales from low cost, standard function to high end features like hot-swap, HART, time tagging, redundancy down to I/O channel.

S800-eA I/O is an open comprehensive, distributed, process I/O system that communicates with controllers by direct connection or over industry-standard field buses. Thanks to its open connectivity it fits a wide range of process controllers from ABB and others.

By permitting installation in the field, close to sensors and actuators, S800-eA I/O reduces the installation cost by reducing the cost of cabling.

サポート或いは製品の購買情報をお探しですか?

Benefits
Technical data
Service
  • Cost effective solutions to practically all needs for field device interfacing, including basic analog and digital I/O, as well as intrinsic safety and high integrity solutions.
  • Highly modular and can be built in a near infinite number of ways, from highly centralized to highly distributed.
  • Supporting industry standard field bus PROFIBUS DP, compatible also with non-ABB controllers; supports also ABB’s Advant Fieldbus 100
  • Configured transparently as part of  parent controllers, like local I/O; no additional knowledge or skills are required.
  • Comprehensive diagnostics, hot swapping of modules and redundancy solutions contribute to keeping production up
Communication interfaces
CI801-eA

PROFIBUS-DP/V1. Hot Configuration in Run & HART® pass-through, GSD-file provided

Digital input modules
DI810-eA

16 ch. for 24 V d.c. inputs with current sinking

DI811-eA

16 ch. for 48 V d.c. inputs with current sinking

DI814-eA

16 ch. for 24 V d.c. inputs with current sourcing

DI818-eA  32 ch. for 24 V d.c. inputs with current sinking
DI820-eA  8 ch. for 110 V a.c./d.c. inputs 
DI821-eA  8 ch. for 220 V a.c./d.c. inputs 
DI825-eA 8 ch. for 125 V d.c. inputs 
DI828-eA 16 ch. for 120 V AC/DC inputs 
DI830-eA 16 ch. for 24 V d.c. inputs with current sinking 
DI831-eA 16 ch. 48 V d.c. inputs with current sinking 
DI840-eA 16 channels for 24 V d.c. inputs with current sinking, extended diagnostics, transmitter power supply 
Digital output modules
DO810-eA

16 ch., 2 groups of 8 ch., 24 V d.c., max 0.5 A, transistor, current source, short-circuit-proof

DO814-eA

16 ch., 2 groups of 8 ch., 24 V d.c., max 0.5 A, transistor, current sink, short-circuit-proof

DO815-eA  8 ch., 2 groups of 4 ch., 24 V d.c., max 2 A, transistor, current source, short-circuit-proof 
DO818-eA  32 ch., 2 groups of 16 ch., 24 V d.c., max 0.5 A, transistor, current source, short-circuit-proof  
DO820-eA  8 ch., separate returns, 5-250 V, max 3 A a.c./d.c., relay (N.O.) 
DO821-eA   8 ch., separate returns, 5-250 V, max 3 A a.c./d.c., relay (N.C.) 
DO828-eA   16 ch., separate returns, 5-250V a.c. / 5-125V d.c. max 2A a.c./d.c., relay (N.O.) 
DO840-eA        16 ch., 1 group of 16 ch., 24 V d.c., max. 0,5 A, current source, short-circuit-proof, extended diagnostics 
Pulse counter
DP820-eA

2 identical independent channels, interface for RS422, 5 V, 12 V, 24 V and 13 mA transducer signal levels

DP840-eA  8 identical independent channels, interface for NAMUR, 12 V and 24 V transducer signal levels 
Analog input modules

AI810-eA

8 ch. for 0...20 mA, 4...20 mA, 0...10 V or 2...10 V d.c., single ended unipolar inputs, 12 bit resolution

AI815-eA 8 ch. for 0...20 mA, 4...20 mA, 0...5 V or 1...5 V d.c., single ended unipolar inputs, 12 bit resolution, HART pass-through communication
AI820-eA  4 ch. for -20...+20 mA, 0...20 mA, 4...20 mA, -10...+10 V, 0...10 V, 2...10 V, -5...+5 V, 0...5 V, 1...5 V d.c. bipolar differential inputs, 14 bit resolution plus sign 
AI825-eA  4 ch. individually galvanic isolated inputs for +20 mA, 0...20 mA, 4...20 mA, +10 V, 0...10 V, 2...10 V, 14 bit resolution plus sign 
AI830A-eA  8 ch. for RTD (Pt100, Cu10, Ni100 and Ni120 and resistor) inputs, 3-wire connection to RTDs, 14 bit resolution  
AI835A-eA 8 ch., (7+ ref. junction), 1 group of 8 ch., TC types B, C, D, E, J, K, L, N, R, S, T, U, -30…75 mV, 15 bit resolution 
AI843-eA   8 ch. + ref. junction, 1 group of 8 ch., TC types: B, C, E, J, K, L, N, R, S, T, U, -30…75 mV, 16 bit resolution, extended diagnostics 
AI845-eA    8 ch. for 0...20 mA, 4...20 mA, 0...5 V or 1...5 V d.c., 1 group of 8 channels isolated from ground, single ended unipolar inputs, single or redundant operation, 12 bit resolution 
Analog Ouput modules

AO810V2-eA

8 ch., 1 group of 8 ch., 0(4)-20 mA, 14 bits, load: max 850 Ohms (short-circuit-proof)

AO815-eA  8 ch., 1 group of 8 ch., 4..20 mA, 12 bit, load: max 750 Ohms (short-circuit-proof ), HART interface 
AO820-eA   4 ch., separate returns, isolated bipolar, +-0(2)-10 V, +-0(4)-20 mA, 12 bits + sign, load: max 550 Ohms (current) / ≥2 kOhms (voltage), short-circuit-proof 
AO845A-eA   8 ch., 1 group of 8 ch., 4-20 mA, 12 bit, load: max 750 Ω (short-circuit-proof) extended diagnostics, HART interface 
Termination unit

TU810V1      

Compact MTU, 16 ch., 50 V, connections to ModuleBus and I/O modules, DIN rail mounting

TU811V1  Compact MTU, 8 ch., 250 V,  connections to ModuleBus and I/O modules, DIN rail mounting  
TU812V1   Compact MTU, 50 V, connections to ModuleBus and I/O modules, DIN rail mounting   
TU813 Compact MTU, 8 ch., voltage > 250 V,  current > 3 A per channel, connections to ModuleBus and I/O modules, DIN rail mounting  
TU814  Compact MTU, 16 I/O channels, 2 process voltage connections, voltage > 250 V,  current > 3 A   
TU818 

Compact MTU, 32 I/O channels, 50 V, connections to ModuleBus and I/O modules, DIN rail mounting 

TU819 Compact MTU, 50 V, up to 32 I/O signals using D-sub 25 connector, connections to ModuleBus and I/O modules, DIN rail mounting   
TU830V1  Extended MTU, 16 ch. of field signals and process power connections, each channel has two I/O connections, one ZP connection, connections to ModuleBus and I/O modules, DIN rail mounting      
TU831V1   Extended MTU, 8 I/O channels,  voltage > 250 V, current > 3 A,  connections to ModuleBus and I/O modules, DIN rail mounting      
TU833 Extended MTU, 16 I/O channels, two process voltage,  voltage > 50 V, current > 2 A, connections to ModuleBus and I/O modules, DIN rail mounting        
TU835V1  Extended MTU, 8 I/O channels, voltage > 50 V, current > 2 A, connections to ModuleBus and I/O modules, DIN rail mounting         
TU836V1  Extended MTU, 8 I/O channels, voltage > 250 V, current > 3 A, each channel has one fused load power terminal and one signal return connection, connections to ModuleBus and I/O modules, DIN rail mounting 
TU837V1 Extended MTU, 8 I/O channels, voltage > 250 V, current > 3 A, each channel has two terminals and one is fused, connections to ModuleBus and I/O modules, DIN rail mounting 
TU838  Extended MTU, 16 I/O ch., voltage > 250 V, current > 3 A, 2 channels share one fused transducer power terminal, connections to ModuleBus and I/O modules, DIN rail mounting 
TU839  Extended MTU, 8 I/O ch., 2 individually isolated, fused groups for sensor power distribution, each group has a 200 mA fuse, connections to ModuleBus and I/O modules, DIN rail mounting 
TU842  Redundant MTU, 16 I/O channels, 2+2 process voltage connections, connections to two ModuleBuses and I/O modules, DIN rail mounting  
TU843  Redundant MTU, 16 I/O channels, 2+2 process voltage connections, each channel has two I/O connections and one ZP connection, voltage > 250 V, current > 3 A, connections to two ModuleBuses and I/O modules, DIN rail mounting  
TU844  Redundant MTU, 8 I/O channels, 2+2 process voltage connections, each channel has two I/O connections and one ZP connection, voltage > 50 V, current > 2 A, connections to two ModuleBuses and I/O modules, DIN rail mounting   
TU845  Redundant MTU, 8 I/O channels, 2+2 process voltage connections, each channel has two I/O connections and one ZP connection, using 2-wire connections and field power distribution, voltage > 50 V, current > 2 A, connections to two ModuleBuses and I/O modules, DIN rail mounting 
TU850  Extended MTU, 8 I/O channels, 2-wire, voltage >50 V, current > 15mA per I/O channel (digital input) or 25mA per two I/O channels (analog input), connections to ModuleBuses and I/O modules, DIN rail mounting  
TU851  Extended MTU, 16 I/O channels, voltage >250 V, current > 3mA per I/O channel connections to ModuleBuses and I/O modules, DIN rail mounting   
TU852  Redundant MTU, 16 channels of field signals and process power connections, using 3-wire connections, DIN rail mounting  
TU854  Redundant MTU, 8 I/O channels, 2+2 process voltage connections, connections to two ModuleBuses and I/O modules, DIN rail mounting   
TU890  Compact MTU, voltage >50 V, current > 2mA per I/O channel, intrinsic safety applications - use with AI890, AI893, AI895, AO890, AO895, DI890 and DO890, DIN rail mounting      
TU891  Compact MTU, voltage >50 V, current > 2mA per I/O channel, intrinsic safety applications - use with AI890, AI893, AI895, AO890, AO895, DI890 and DO890, connections to ModuleBuses and I/O modules, DIN rail mounting   

Related links