Testing and analysis for several drive performance indicators measures performance and identifies improvement area potential.
These areas include:
Diagnostic data is collected for each drive under typical production conditions for a single grade. The data is evaluated by comparing measurements to limits specified for each drive-motor combination.
The following is the list of measurement points and general guidelines for assessing the condition of individual drives:
- FPM: Surface speed of the roll or section
- Motor Rated Current: Motor nameplate data
- Motor Actual Current: Should not exceed the rated current.
- Motor Torque %: Motor torque (filtered value) should never exceed or run near 100%, and torque variations exceeding the baseline reading +/-10% should be investigated.
Encoder Feedback Ripple: The lowest possible values for ripple are desirable, however any value of 75 units or higher should be investigated. Misalignment of encoder, defective encoder coupling or bad bearings in encoder are problems typically causing high than normal readings.