Voltage | 380 - 480 V ± 10%
(Other voltages via transformer) |
Power System | 3-Phase |
Nominal supply frequency | 50 Hz or 60 Hz |
Frequency tolerance | ± 5 Hz |
Overvoltage category | III |
Max Fault Capacity | 65 kA |
Efficiency | > 97.7% (@ 480 V) |
Overload and short circuit protection | Current limited output (200%) |
Capacity Rating | 100 kVA to 2000 kVAr
(other ratings by request) |
Harmonic correction | yes |
Imbalance current capability | 25% of nominal current |
Marking | CE, C-Tick |
Electrical Equipment for use in Power Installations | IEC 62103 |
Electromagnetic compatibility (EMC) | CISPR 11 |
IEC Pollution degree rating | 2 |
Operating temperature | 0°C to 50°C (de-rate -2% current per 1°C above 40°C) |
Capacity de-rating with altitude | 1.0% / 100 m for application above 1000 m, 2000 m maximum |
Humidity | < 95%, non-condensing |
Noise | < 75dBA typical @ 1 m |
Enclosure IP rating | IP20 / NEMA 1 (standard) |
HMI (GDM) panel IP rating | IP54 (from front) |
Material | Electro-galvanized steel |
Color | RAL7035 |
Panel thickness side & rear | 1.5 mm |
Panel thickness door | 2 mm |
Enclosure Access | Left hand hinged doors with key lock |
User Interface | 8.4” color LCD touch panel |
Communications type | Ethernet |
Functions | HTML server (monitoring only)
Modbus-TCP (monitoring only) |
Technical specifications are subject to change without notice.