PCS100 RPC technical specifications

Are you looking for support or purchase information?

Utility Connection

Voltage

380 - 480 V ± 10%
(Other voltages via transformer)

Power System
3-Phase

Nominal supply frequency

50 Hz or 60 Hz

Frequency tolerance

± 5 Hz

Overvoltage category

III
Max Fault Capacity
65 kA
Efficiency > 97.7% (@ 480 V)
Overload and short circuit protection
Current limited output (200%)

Ratings

Capacity Rating

100 kVA to 2000 kVAr 
(other ratings by request)

Harmonic correction

yes

Imbalance current capability

25% of nominal current

Standards and Certifications
Marking
CE, C-Tick
Electrical Equipment for use in Power Installations
IEC 62103
Electromagnetic compatibility (EMC)
CISPR 11 
 Environmental  
IEC Pollution degree rating
2
Operating temperature
0°C to 50°C (de-rate -2% current per 1°C above 40°C)
Capacity de-rating with altitude
1.0% / 100 m for application above 1000 m, 2000 m maximum
Humidity
< 95%, non-condensing
Noise
< 75dBA typical @ 1 m
Enclosure  
Enclosure IP rating
IP20 / NEMA 1 (standard)
HMI (GDM) panel IP rating
IP54 (from front)
Material
Electro-galvanized steel
Color
RAL7035
Panel thickness side & rear
1.5 mm
Panel thickness ­door 2 mm
Enclosure Access Left hand hinged doors with key lock
 User interface  
User Interface 8.4” color LCD touch panel
Communications type Ethernet
 Functions HTML server (monitoring only)
Modbus-TCP (monitoring only)

Technical specifications are subject to change without notice. 

 