Field Information Manager 3.0:
The OPC UA server of Field Information Manager is a standard server which becomes active after importing a suitable license.
Certificates between client and server have to be exchanged in order to establish a trustworthy connection:
- The server certificate of Field Information Manager can be exported via Tools Menu - OPTIONS - CLIENT/SERVER SETTINGS - OWN CERTIFICATE.
It must be installed at the OPC UA client machine according to the requirements of the used client software.
- The client certificate must be added as a trusted certificate via Tools Menu - OPTIONS - CLIENT/SERVER SETTINGS - TRUSTED CERTIFICATES.
A connection can be built up by using the IP address of the Field Information Manager node and the port number (default: 48030). All connected OPC UA clients are displayed in Tools Menu - OPTIONS - CLIENT/SERVER SETTINGS - CONNECTIONS.
Note:
The security policy can be defined in Tools Menu - OPTIONS - OPC UA SERVER SETTINGS and defines the level of security applied to the communication between the tool and connected OPC UA clients. Please note that the selected setting must match with used OPC UA clients.
___________________________________________________________________________
Field Information Manager 2.5 or older:
The OPC UA server of Field Information Manager is a standard server which becomes active after importing a suitable license.
Certificates between client and server have to be exchanged in order to establish a trustworthy connection:
- The server certificate of Field Information Manager is found in the following directory:
"C:\ProgramData\ABB\Field Information Manager\CertificateStores\certs".
It must be installed at the OPC-UA client machine according to the requirements of the used client software.
- The client certificate must be installed to the store "ABB.FIM.TrustedPeople" using
standard Windows mechanisms.
A connection can be built up by using the IP address of the Field Information Manager node and the port number (default: 48030).